UPS ATLANTIS A03-OP10002P-RC 10000VA, 9000W RACK 6U (3+3) DOPPIA CONV.-INTERF.EPO-16 BATT.

Disponibilità: ultimi pezzi rimasti

1.830,57 € + iva
2.233,30 € iva già inclusa

EAN-13 : 8026974022833

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

UPS ATLANTIS A03-OP10002P-RC 10000VA 9000W RACK 6U 3 3 DOPPIA CONV. -INTERF. EPO-16 BATT ...

Richiedi info o prenota

UPS ATLANTIS A03-OP10002P-RC 10000VA/9000W RACK 6U (3+3) DOPPIA CONV.-INTERF.EPO-16 BATT. 12V/9A -SLOT X SK SNMP


Power Rating (VA): 10000
Power (W): 9000


Input (Low Line Transfer):
- 80VAC-300VAC (load <=30%±5%)
- 140VAC-300VAC <=60%±5%)
- 160VAC-300VAC (load <=80%±5%)
- 190VAC-300VAC <=100%±5%)
Frequency Range: 45-55Hz / 54-66Hz
Power Factor: >0,99 (Normal Voltage)


Output
- Voltage: 208/220/230/240VAC
- AC Voltage Regulation: ±1%
- Frequency Range: 50Hz (±0.5%) or 60Hz (±0.5%)
- Waveform: Pure SineWave
- Crest Ratio: 3:1 (Max)
- Harmonic Distortion: <2% THD (liner Load) | <5% THD (Non liner Load)


Transfer:
- AC->Battery: Zero
- INV->ByPass: Less than 4ms (typical)
WaveForm (Batt. Mode): Pure Sinewave


Efficiency:
- AC Mode = 92%
- Battery 90%
- ECO = 96%


Battery
- Voltage: 192VDC
- Capacity: 12V/9.0Ah
- Quantity: 16
- Recharge Time: 6 hours to (90%)
- Type: Sealed Maintenance Free Lead Acid VRLA Type
- Design: Easy-swappable battery design
- Charging Voltage: 218.4 VDC ±1%
- Charging I: 1.0A Max


Indicators LCD Display
- UPS status | Load level Battery | Input/Output/battery info Discharge time and Fault indicators


Backup Times:
- 2700w up to 3:20m
- 2025w up to 5:20m
- 1350w up to 11m
- 675w up to 25m


Protection:
- 105%< Overload AC <110% Warning UPS transfers to ByPass after 10 minutes
- 110%< Overload AC <130% Warning UPS transfers to ByPass after 1 minutes
- Overload AC >130% Warning UPS transfers to ByPass after 3 seconds 
- 105%< Overload Battery <110% Warning UPS shut down after 10 minutes
- 110%< Overload Battery <130% Warning UPS shut down after 1 minute
- Overload AC >130% Warning shut down after 3 seconds 
- 110%< ByPass <120% Overload Warning UPS shut down after 30 minutes
- 120%< ByPass <130% Overload Warning UPS shut down after 10 minutes
- ByPass >130%  Overload Warning UPS shut down after 1 minute
- Overload Inverter (>100%)
- Short Circuit INV: Electric Circuit
- Short Circuit AC: ICB & Electric Circuit
- Battery Over-drain Two stages: Controlled Battery Low Warning & Cut Off
- High Surge Level Immunity (>7KV)


Advanced:
- Fan detect protection and Fan speed control
- ECO mode


Connections
- Terminal Block
- RS232 and USB(HID)
- Intelligent Slot for SNMP Card (A03-SNMP2-IN)
- EPO/ROO
- Battery Box Connection


Dimensions (WxHxD):
- Ups: 438 x 131 (3U) 480 mm
- Battery Pack: 438 x 131 (3U) 680 mm


Weight: 70,0 Kg
Noise Level: Less then 55 dBA @ 1.0 meter (battery full charged, without buzzer)
Temperature: 0°-40° C
Humidity: 20-90% (non-condensing)

Ultima revisione scheda prodotto: 03-02-2023 23:43

Aggiungi al carrello

Richiedi info o prenota

Ci impegnamo costantemente ad aggiornare le schede dei prodotti che trovi in questo portale ma, utilizzando anche sistemi automatici per la gestione delle disponibilità ed affini alle schede del prodotto, a volte queste ultime possono non essere precise. Non rilasciamo alcuna garanzia né dichiarazione in relazione all'accuratezza delle informazioni. Se hai bisogno di maggiori info, prima dell'acquisto, ti invitiamo a contattarci da questa pagina così da offrirti ogni informazione che cerchi. Le immagini possono non rispecchiare il reale prodotto che riceverai.